Where can I find the earth loop impedance (Zs) for the GV2 TeSys motor circuit breakers?

The charts below detail the Earth Loop impedance (Zs) for the GV2 range for any TN system based on the British Standard BS7671:2008+A3:2015

Two documents are also attached:
1) Sheet with Zs charts of Tesys motor circuit breakers:
  • Tesys GV2
  • Tesys GV3
  • Tesys GV4
  • Tesys GV7
  • Tesys U
2) Explaination of the calculation of the maximum Earth Loop Impedancee
This also includes additional information about:
  • Motor Rated devices
  • Ambient Temperature
Tesys GV2 Range
Please refer to the charts below that detail the maximum earth loop impedance Zs for 0.4s disconnection time with Uo 230V
 
GV2ME
Reference Thermal Adjustment
Range In
Magnetic Tripping Current Im Tolerance
Im+20%
Maximum Loop
Impedance Zs
  (A) (A) (A) (Ω) 
GV2-ME01 0.1 .. 0.16 1.50 1.80 121.39
GV2-ME02 0.16 .. 0.25 2.40 2.88 75.87
GV2-ME03 0.25 .. 0.4 5.00 6.00 36.42
GV2-ME04 0.4 .. 0.63 8.00 9.60 22.76
GV2-ME05 0.63 .. 1 13.00 15.60 14.01
GV2-ME06 1 .. 1.6 22.50 27.00 8.09
GV2-ME07 1.6 .. 2.5 33.50 40.20 5.44
GV2-ME08 2.5 .. 4 51.00 61.20 3.57
GV2-ME10 4 .. 6.3 78.00 93.60 2.33
GV2-ME14 6 .. 10 138.00 165.60 1.32
GV2-ME16 9 .. 14 170.00 204.00 1.07
GV2-ME20 13 .. 18 223.0 267.6 0.82
GV2-ME21 17 .. 23 327.0 392.4 0.56
GV2-ME22 20 .. 25 327.0 392.4 0.56
GV2-ME32 24 .. 32 416.0 499.2 0.44
         
GV2P
Reference Thermal Adjustment
Range In
Magnetic Tripping Current Im Tolerance
Im+20%
Maximum Loop
Impedance Zs
  (A) (A) (A) (Ω) 
GV2-P01 0.1 .. 0.16 1.50 1.80 121.39
GV2-P02 0.16 .. 0.25 2.40 2.88 75.87
GV2-P03 0.25 .. 0.4 5.00 6.00 36.42
GV2-P04 0.4 .. 0.63 8.00 9.60 22.76
GV2-P05 0.63 .. 1 13.00 15.60 14.01
GV2-P06 1 .. 1.6 22.50 27.00 8.09
GV2-P07 1.6 .. 2.5 33.50 40.20 5.44
GV2-P08 2.5 .. 4 51.00 61.20 3.57
GV2-P10 4 .. 6.3 78.00 93.60 2.33
GV2-P14 6 .. 10 138.00 165.60 1.32
GV2-P16 9 .. 14 170.00 204.00 1.07
GV2-P20 13 .. 18 223.0 267.6 0.82
GV2-P21 17 .. 23 327.0 392.4 0.56
GV2-P22 20 .. 25 327.0 392.4 0.56
GV2-P32 24 .. 32 416.0 499.2 0.44
         
GV2L
Reference Thermal Adjustment
Range In
Magnetic Tripping Current Im Tolerance
Im+20%
Maximum Loop
Impedance Zs
  (A) (A) (A) (Ω) 
GV2-L03 0.4 5.00 6.00 36.42
GVL-L04 0.63 8.00 9.60 22.76
GV2-L05 1 13.00 15.60 14.01
GV2-L06 1.6 22.50 27.00 8.09
GV2-L07 2.5 33.50 40.20 5.44
GV2-L08 4 51.00 61.20 3.57
GV2-L10 6.3 78.00 93.60 2.33
GV2-L14 10 138.00 165.60 1.32
GV2-L16 14 170.00 204.00 1.07
GV2-L20 18 223.0 267.6 0.82
GV2-L22 25 327.0 392.4 0.56
GV2-L32 32 416.0 499.2 0.44
         
GV2LE
Reference Thermal Adjustment
Range In
Magnetic Tripping Current Im Tolerance
Im+20%
Maximum Loop
Impedance Zs
  (A) (A) (A) (Ω) 
GV2-LE03 0.4 5.00 6.00 36.42
GVL-LE04 0.63 8.00 9.60 22.76
GV2-LE05 1 13.00 15.60 14.01
GV2-LE06 1.6 22.50 27.00 8.09
GV2-LE07 2.5 33.50 40.20 5.44
GV2-LE08 4 51.00 61.20 3.57
GV2-LE10 6.3 78.00 93.60 2.33
GV2-LE14 10 138.00 165.60 1.32
GV2-LE16 14 170.00 204.00 1.07
GV2-LE20 18 223.0 267.6 0.82
GV2-LE22 25 327.0 392.4 0.56
GV2-LE32 32 416.0 499.2 0.44
         
GV2RT
Reference Thermal Adjustment
Range In
Magnetic Tripping Current Im Tolerance
Im+20%
Maximum Loop
Impedance Zs
  (A) (A) (A) (Ω) 
GV2-RT03 0.25 .. 0.4 8.00 9.60 22.76
GV2-RT04 0.4 .. 0.63 13.00 15.60 14.01
GV2-RT05 0.63 .. 1 22.00 26.40 8.28
GV2-RT06 1 .. 1.6 33.00 39.60 5.52
GV2-RT07 1.6 .. 2.5 51.00 61.20 3.57
GV2-RT08 2.5 .. 4 78.00 93.60 2.33
GV2-RT10 4 .. 6.3 138.00 165.60 1.32
GV2-RT14 6 .. 10 200.00 240.00 0.91
GV2-RT16 9 .. 14 280.0 336.0 0.65
GV2-RT20 13 .. 18 400.0 480.0 0.46
GV2-RT21 17 .. 23 400.0 480.0 0.46
Was this helpful?