How do I assign Sepam Equation Editor variables to output contacts?

Issue
User needs to assign Sepam Equation Editor variables to output contacts on a Sepam relay

Product Line
Sepam series 40
Sepam series 80

Environment
SFT2841 

Resolution
The global equation editor variables (form V1, V2, V3, NOT VL1, VL2, etc) may be assigned to the output contacts on the Sepam relay in the Control Matrix. 

Please note that on Sepam series 40, global equation editor variables cannot be assigned to output contact O4 because O4 is the watchdog. O4 will be grayed out in the Control Matrix.
Similarly, on Sepam series 80, global equation editor variables cannot be assigned to output contact O5 as O5 is the watchdog on Sepam series 80. O5 will be grayed out in the Control Matrix.



If outputs O1 and O11 (Sepam series 40) or O1 and O101 (Sepam series 80) are gray, CB control is set to on. The only way to assign the global equation editor variables to one of these contacts is to turn CB control off.

Note: Setting CB Control to off disables the Circuit Breaker Control functionality of the relay.