Which registers do I need to write to control the outputs on a PM5000 series meter?

Use the register 5000 to write the command. Commands 6002 and 6003 are for De-energizing and Energnizing Digital Output.
These are unprotected commands, so it is not required to read the semaphore value.

See attachment for more details