Ireland
Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

variable speed drive ATV312 - 0.37kW - 1kVA - 41 W - 200..240 V - 1-phase supply

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Altivar 312
    product or component type
    Variable speed drive
    product destination
    Asynchronous motors
    product specific application
    Simple machine
    assembly style
    With heat sink
    component name
    ATV312
    motor power kW
    0.37 kW
    motor power hp
    0.5 hp
    [Us] rated supply voltage
    200...240 V - 15...10 %
    supply frequency
    50...60 Hz - 5...5 %
    network number of phases
    Single phase
    line current
    5.3 A at 200 V, Isc = 1 kA
    4.4 A at 240 V
    EMC filter
    Integrated
    apparent power
    1 kVA
    maximum transient current
    5 A for 60 s
    power dissipation in W
    41 W at nominal load
    speed range
    1…50
    asynchronous motor control profile
    Factory set : constant torque
    Sensorless flux vector control with PWM type motor control signal
    electrical connection
    Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5 mm² AWG 14
    L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 2.5 mm² AWG 14
    supply
    Internal supply for logic inputs: 19...30 V 100 mA, protection type: overload and short-circuit protection
    Internal supply for reference potentiometer (2.2 to 10 kOhm): 10...10.8 V 10 mA, protection type: overload and short-circuit protection
    communication port protocol
    Modbus
    CANopen
    IP degree of protection
    IP20 on upper part without cover plate
    IP21 on connection terminals
    IP31 on upper part
    IP41 on upper part
    option card
    Communication card for CANopen daisy chain
    Communication card for DeviceNet
    Communication card for Fipio
    Communication card for Modbus TCP
    Communication card for Profibus DP
    Complementary
    supply voltage limits
    170…264 V
    network frequency
    47.5...63 Hz
    prospective line Isc
    1 kA
    continuous output current
    3.3 A at 4 kHz
    output frequency
    0…500 kHz
    nominal switching frequency
    4 kHz
    switching frequency
    2...16 kHz adjustable
    transient overtorque
    170…200 % of nominal motor torque
    braking torque
    150 % during 60 s with braking resistor
    100 % with braking resistor continuously
    150 % without braking resistor
    regulation loop
    Frequency PI regulator
    motor slip compensation
    Automatic whatever the load
    Suppressable
    Adjustable
    output voltage
    <= power supply voltage
    tightening torque
    Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6: 0.6 N.m
    L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 0.8 N.m
    insulation
    Electrical between power and control
    analogue input number
    3
    analogue input type
    AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance: 30000 Ohm
    AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm
    AI3 configurable current 0...20 mA, impedance: 250 Ohm
    sampling duration
    AI1, AI2, AI3: 8 ms analog
    LI1...LI6: 4 ms discrete
    response time
    AOV, AOC 8 ms for analog
    R1A, R1B, R1C, R2A, R2B 8 ms for discrete
    linearity error
    +/- 0.2 % for output
    analogue output number
    1
    analogue output type
    AOC configurable current: 0...20 mA, impedance: 800 Ohm, resolution: 8 bits
    AOV configurable voltage: 0...10 V, impedance: 470 Ohm, resolution: 8 bits
    discrete input logic
    Logic input not wired (LI1...LI4), < 13 V (state 1)
    Negative logic (source) (LI1...LI6), > 19 V (state 0)
    Positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1)
    discrete output number
    2
    discrete output type
    Configurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC - 100000 cycles
    Configurable relay logic: (R2A, R2B) NC - 100000 cycles
    minimum switching current
    R1-R2 10 mA at 5 V DC
    maximum switching current
    R1-R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms
    R1-R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms
    R1-R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms
    R1-R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms
    discrete input number
    6
    discrete input type
    (LI1...LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm
    acceleration and deceleration ramps
    S, U or customized
    Linear adjustable separately from 0.1 to 999.9 s
    braking to standstill
    By DC injection
    protection type
    Input phase breaks: drive
    Line supply overvoltage and undervoltage safety circuits: drive
    Line supply phase loss safety function, for three phases supply: drive
    Motor phase breaks: drive
    Overcurrent between output phases and earth (on power up only): drive
    Overheating protection: drive
    Short-circuit between motor phases: drive
    Thermal protection: motor
    insulation resistance
    >= 500 mOhm 500 V DC for 1 minute
    local signalling
    Drive voltage: 1 LED (red)
    CANopen bus status: four 7-segment display units
    time constant
    5 ms for reference change
    frequency resolution
    Analog input: 0.1...100 Hz
    Display unit: 0.1 Hz
    connector type
    1 RJ45 for Modbus/CANopen
    physical interface
    RS485 multidrop serial link
    transmission frame
    RTU
    transmission rate
    10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen
    4800, 9600 or 19200 bps for Modbus
    number of addresses
    1…127 for CANopen
    1…247 for Modbus
    number of drive
    127 for CANopen
    31 for Modbus
    marking
    CE
    operating position
    Vertical +/- 10 degree
    height
    145 mm
    width
    72 mm
    depth
    132 mm
    product weight
    1.5 kg
    Environment
    dielectric strength
    2040 V DC between earth and power terminals
    2880 V AC between control and power terminals
    electromagnetic compatibility
    1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
    Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
    Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
    standards
    IEC 61800-5-1
    IEC 61800-3
    product certifications
    UL
    C-Tick
    NOM
    CSA
    DNV
    GOST
    pollution degree
    2
    protective treatment
    TC
    vibration resistance
    1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
    1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
    shock resistance
    15 gn for 11 ms conforming to EN/IEC 60068-2-27
    relative humidity
    5…95 % without condensation conforming to IEC 60068-2-3
    5…95 % without dripping water conforming to IEC 60068-2-3
    ambient air temperature for storage
    -25…70 °C
    ambient air temperature for operation
    -10…50 °C without (with protective cover on top of the drive)
    -10…60 °C with derating factor (without protective cover on top of the drive)
    operating altitude
    <= 1000 m without
    1000...2000 m with current derating 1 % per 100 m
    Contractual warranty
    Warranty
    18 months
  • Documents and Downloads

    Language
    • English
    • Chinese
    Catalogue
    Date
    Size
    Add to My Documents
    Altivar 312 variable speed drives catalogue (Version 3.0)
    User guide
    Date
    Size
    Add to My Documents
    ATV312 PROFIBUS DP communication manual (Version 02)
    ATV312 to ATV320 Migration Manual (Version 01)
    1) ATV312 getting Started (Version 04)
    Date 16/06/17
    Size 1.6 MB
    2_ATV312 Installation Manual (Version 02)
    Date 14/12/17
    Size 2.3 MB
    3) ATV312 programming manual (Version 04)
    Date 13/12/17
    Size 1.8 MB
    1) ATV312 Getting Stated Annex : SCCR (Version 04)
    ATV312 CANopen manual (Version 03)
    Date 14/12/17
    Size 1.9 MB
    ATV312 DeviceNet manual (Version 02)
    Date 14/12/17
    Size 2.8 MB
    CAD
    Date
    Size
    Add to My Documents
    CAD for ATV312H037M2: variable speed drive ATV312 - 0.37kW - 1kVA - 41 W - 200..240 V - 1-phase supply (Version 1.0)
    CAD file (on TraceParts) for ATV312H037M2: variable speed drive ATV312 - 0.37kW - 1kVA - 41 W - 200..240 V - 1-phase supply (Version 2.0)
    Certificate
    Date
    Size
    Add to My Documents
    ATV31-312 CSA CERTIFICATE (Version 1.0)
    Date 19/06/18
    Size 71.9 KB
    ATV312 C-TICK CERTIFICATE (Version 1.0)
    Date 19/06/18
    Size 527.5 KB
    ATV312 EU DECLARATION (Version 1.0)
    Date 27/04/18
    Size 599.1 KB
    ATV31 312 UL CERTIFICATE (Version 1.0)
    Date 13/06/19
    Size 741.2 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Instruction Sheet substitution ATV31-ATV312 (Version 01)
    Instruction sheet - fan VZ3V3104 (Version 02)
    Date 30/10/18
    Size 675.9 KB
    Instruction sheet - Fan: VZ3V3101, VZ3V3102 (Version 04)
    Catalogue page
    Date
    Size
    Add to My Documents
    Variable speed drives ATV 312 (Version 3.0)
    Date 14/08/18
    Size 67.8 KB
    Marine certificate
    Date
    Size
    Add to My Documents
    DNV-GL Marine Ceritifacte Altivar ATV312 variable speed drive (Version 1.0)
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    Altivar 312 range 0.18 to 15KW, Product Environmental Profile (Version 1.0)
    Instruction Sheet: China RoHS - Hazardous Substances Table (Version 01)
    System user guide
    Date
    Size
    Add to My Documents
    Compact Hardwired Logic Controller M221, System User Guide (Version 00)
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.