Ireland

Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

Display & switch ZMLP - 24VDC - 4..20 mA - PNP - window - M12

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    OsiSense XM
    product or component type
    Electronic pressure sensors
    device short name
    ZMLP
    Complementary
    display range
    -14.5...6000
    [Us] rated supply voltage
    24 V DC SELV, voltage limit: 17...33 V
    current consumption
    <= 50 mA
    electrical connection
    M12 female connector with 2 pins
    M12 male connector with 4 pins
    type of output signal
    Analogue + discrete
    analogue output function
    4...20 mA
    discrete output type
    PNP solid state - NO/NC programmable
    switching function
    Window
    maximum switching current
    200 mA
    voltage drop
    <= 2 V
    adjustable range of switching point on rising pressure
    5...98 % of selected display range
    adjustable range of switching point on falling pressure
    2...95 % of selected display range
    minimum differential travel
    3 % of selected display range
    marking
    CE
    front material
    Polyester
    housing material
    PBT Valox
    operating position
    Any position
    protection type
    Overload protection
    Overvoltage protection
    Reverse polarity
    Short-circuit protection
    response time on output
    <= 3 ms for analog output
    <= 3 ms for discrete output
    display type
    4 digits 7 segments
    local signalling
    1 LED yellow for light ON when switch is actuated
    response time
    300 ms
    delay first up
    <= 100 ms
    accuracy
    <= - 0.1 % of the measuring range
    measurement accuracy
    <= 1 % of the measuring range
    display accuracy
    <= 1 % of the measuring range
    mechanical durability
    >= 10000000 cycles
    depth
    42 mm
    height
    77 mm
    width
    41 mm
    product weight
    0.103 kg
    [Uimp] rated impulse withstand voltage
    0.5 kV DC
    Environment
    product certifications
    cULus
    EAC
    standards
    EN/IEC 61000-6-2
    EN/IEC 61000-6-4
    UL 508
    ambient air temperature for operation
    -25...70 °C
    ambient air temperature for storage
    -30...80 °C
    IP degree of protection
    IP65 conforming to EN/IEC 60529
    IP67 conforming to EN/IEC 60529
    IP69K conforming to DIN 40050
    vibration resistance
    5 gn at 10...2000 Hz conforming to EN/IEC 60068-2-6
    shock resistance
    25 gn conforming to EN/IEC 60068-2-27
    electromagnetic compatibility
    Immunity to conducted RF disturbances at 10 V, 0.15...80 MHz conforming to EN/IEC 61000-4-6
    Surge immunity test at 1 kV conforming to EN/IEC 61000-4-5
    Electrical fast transient/burst immunity test at 2 kV conforming to EN/IEC 61000-4-4
    Susceptibility to electromagnetic fields at 10 V/m, 80...2000 MHz conforming to EN/IEC 61000-4-3
    Electrostatic discharge immunity test at 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



    Dimensions
    Switch with Metal Bracket for Fixing Horizontally



    Dimensions
    Switch with Metal Bracket for Fixing Vertically or on an Inlet Pipe



  • Connections and Schema

    Connections and Schema
    Output M12 Male Connector Wiring


    (1)
    Out
    (2)
    I Out


    Connections and Schema
    Input M12 Female Connector Wiring


    (1)
    l in = 4-20 mA


  • Performance Curves

    Analog Output Description

    The 4…20 mA analog output is strictly the image of the pressure transmitter output signal.


    X :
    Pressure
    Y :
    Analog output signal


    Switching Output Description. Window Mode

    The window switching mode is typically used for the pressure regulation applications


    X :
    Time
    Y :
    Pressure
    (1)
    Output
    NP :
    Nominal pressure
    FH :
    High switching point (adjustable from 5 % to 98 % NP)
    FL :
    Low switching point (adjustable from 2 % to 95 % NP)